SECTION 08900 - STEEL FIRE-RATED GLAZED CURTAIN WALL
PART 1 - GENERAL
1.1 Summary
A. Section Includes:
1.Fire-rated curtain wall systems, including perimeter trims, stools, accessories, shims and anchors, and perimeter sealing of curtain wall framing.
B. Related Sections include the following:
1.Section 07843 - Fire-Resistive Joint Systems for perimeter fire-containment systems (safing insulation) field installed with steel fire-rated glazed curtain-wall systems.
2.Section 07920 - Joint Sealants for installation of joint sealants installed with steel fire-rated glazed curtain-wall systems and for sealants to the extent not specified in this Section.
3.Section 08110 - Steel Doors and Frames for fire-rated doors.
4.Section 08310 - Sliding Doors.
5.Section 08410 - Aluminum Entrances and Storefronts for entrance [and storefront] systems installed with steel fire-rated glazed curtain-wall systems.
6.Section 08520 - Aluminum Windows for nonfire-rated glass and framing.
7.Section 08710 - Door Hardware for door hardware not provided by this Section.
8.Section 08810 - Fire Rated Glass and Framing Systems - Heat Barrier Series for fire-rated doors.
9.Section 08113 - Fire Rated Glass And Framing Systems - Designer Series for fire-rated doors.
10. Section -8910 - Metal Framed Curtain Wall for nonfire-rated glass and framing.
11. Section 08960 - Slope Glazing Systems for nonfire-rated glass and framing.
1.2 PERFORMANCE REQUIREMENTS
A. General: Provide steel fire-rated glazed curtain-wall systems, including anchorage, capable of withstanding, without failure, the effects of the following:
1.Structural loads.
2.Thermal movements.
3.Movements of supporting structure indicated on Drawings including, but not limited to, story drift, twist, column shortening, long-term creep, and deflection from uniformly distributed and concentrated live loads.
Specify dimensional tolerances for support system and adjacent construction in other Sections of this Project's Specifications.
4.Dimensional tolerances of building frame and other adjacent construction.
5.Failure includes the following:
a. Deflection exceeding specified limits.
b. Thermal stresses transferred to building structure.
c. Framing members transferring stresses, including those caused by thermal and structural movements, to glazing.
d. Noise or vibration created by wind and thermal and structural movements.
e. Loosening or weakening of fasteners, attachments, and other components.
f. Sealant failure.
B. System Description:
1.Steel fire-rated glazed curtain wall system, outside glazed pressure plate, cover cap format.
2.Face Widths Available:
a. 1 3/4-inch.
b. 2 3/8-inch wide.
3.Water Drainage:
a. System is vertically weeped. No joint plugs or weep holes at horizontal mullions. Horizontal gaskets are notched and received by vertical gaskets.
C. Structural Loads:
1.Uniform Wind Load: ASTM E 330; Static air design load of 40 psf applied in positive and negative direction; no deflection in excess of L/175 of span of any framing member at design load.
2.At structural test load equal to 1.5 times specified design load, no glass breakage or permanent set in the framing members in excess of 0.2% of their clear spans shall occur.
Delete two subparagraphs below if not applicable. See Evaluations.
3.Seismic Loads: [As indicated on Drawings] <Insert specific loads>.
4.Periodic Maintenance-Equipment Loads: [As indicated on Drawings] <Insert specific loads>.
D. Air Infiltration: ASTM E 283; Air infiltration rate shall not exceed 0.06 cfm/ft2 at a static air pressure differential of 6.24 psf.
E. Water Resistance, (static): ASTM E 331; No leakage at a static air pressure differential of 30 psf as defined in AAMA 501.
F. Water Resistance, (dynamic): AAMA 501.1; No leakage at an air pressure differential of 30 psf as defined in AAMA 501.
G. Thermal Movements: Provide steel fire-rated glazed curtain-wall systems that allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures. Base engineering calculation on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
Differential values below (for aluminum in particular) are suitable for most of the U.S. Revise to suit local conditions and metal color and finish.
1.Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
1.3 Submittals
A. Submit in accordance with Section <Insert Section #>.
B. Product Data: Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of product indicated.
C. Shop Drawings: Prepared by or under the supervision of a qualified professional engineer detailing fabrication and assembly of steel fire-rated glazed curtain-wall systems.
Professional engineer qualifications are specified in Division 1 Section "Quality Requirements."
1.Include structural analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
D. Samples for Initial Selection: For units with factory-applied color finishes.
1.4 QUALITY ASSURANCE
A. Installer Qualifications: Installer experienced (as determined by contractor) to perform work of this section who has specialized in the installation of work similar to that required for this project and who is acceptable to product manufacturer.
1.Engineering Responsibility: Preparation of data for glazed curtain-wall systems including the following:
Retain subparagraph below if engineering is limited to analysis of standard assemblies.
a. Shop Drawings based on testing and engineering analysis of manufacturer's standard units in assemblies similar to those indicated for this Project and submission of reports of tests performed on manufacturer's standard assemblies.
Retain subparagraph below for custom systems.
b. Shop Drawings and comprehensive engineering analysis by a qualified professional engineer.
B. Manufacturer Qualifications: Manufacturer capable of providing field service representation during construction, approving acceptable installer and approving application method.
Retain first subparagraph below for large-scale mockup or include in Division 1 Section "Quality Requirements." Indicate on Drawings the portion of wall represented by mockup or draw mockup as separate element. Coordinate requirements with those in other Sections specifying glazing and cladding materials installed with curtain-wall systems.
C. Pre-Installation Meetings: Conduct pre-installation meeting to verify project requirements, substrate conditions, manufacturer's installation instructions, and manufacturer's warranty requirements.
1.5 Delivery, Storage, and Handling
A. Ordering: Comply with manufacturer's ordering instructions and lead time requirements to avoid construction delays.
B. Packing, Shipping, Handling, and Unloading: Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact.
C. Storage and Protection: Store materials protected from exposure to harmful weather conditions. Handle material and components to avoid damage. Protect curtainwall material against damage from elements, construction activities, and other hazards before, during and after curtainwall installation.
1.6 PROJECT CONDITIONS
A. Field Measurements: Verify actual locations of structural supports for steel fire-rated glazed curtain-wall systems by field measurements before fabrication and indicate measurements on Shop Drawings.
Delete below if not allowed.
1.Established Dimensions: Where field measurements cannot be made without delaying the Work, establish dimensions and proceed with fabricating steel fire-rated glazed curtain-wall systems without field measurements. Coordinate construction to ensure that actual dimensions correspond to established dimensions.
1.7