Features
- Fire-rated for 20-90 minutes with required hose stream test
- Impact safety-rated-meets ANSI Z97.1 and CPSC 16CFR1201 (Cat. I and Cat. II)
- Wired glass with high performance surface-applied fire-rated film
- Available in Diamond Clear (3/4" pattern) and Georgian Clear (1/2" pattern)
- Available as an insulated glass unit (IGU)
- Withstands thermal shock
- Passes positive pressure test standards UL 10C, UBC 7-2 and UBC 7-4
Note: This product is not a barrier to radiant heat. This product does not meet test standards ASTM E-119 or UL 263. If your jurisdiction requires a "barrier to heat" product, please see Pilkington Pyrostop.
Listings

Listed and labeled by Underwriters Laboratories, Inc.® and Underwriters Laboratories of Canada. Test report number for labeled fire-rated assemblies is UL File No. R13377. Tests performed in accordance with UL 9, UL 10C, ASTM E2074, ASTM E2010, NFPA 252, NFPA 257, UBC 7-2, UBC 7-4.
Standard Sizes
| Rating |
Assembly |
Max. Exposed
Area (in2/ft2) |
Max. Width
Of Exposed
Glazing (in) |
Max. Height
Of Exposed
Glazing (in) |
|
20 min.
|
Doors (non-temp rise)
|
3,289/22.84
|
34-3/4
|
92
|
|
45 min.
|
Doors (non-temp rise)
|
1,296/9
|
54
|
54
|
|
|
Other than doors
|
1,296/9
|
54
|
54
|
|
|
|
60-90 min.
|
Doors
|
100/.69
|
10
|
33
|
|
|
|
|
|
|
Sizes When Glazed With Pemko FG3000™
| Rating |
Assembly |
Max. Exposed
Area (in2/ft2) |
Max. Width
Of Exposed
Glazing (in) |
Max. Height
Of Exposed
Glazing (in) |
|
45 min.
|
Doors (non-temp rise)
|
2,856/19.83
|
34
|
84
|
|
|
Other than doors
|
4,608/32
|
100
|
100
|
|
|
|
60 min.
|
Wood Door (non-temp rise)
|
960/6.66
|
12
|
80
|
|
90 min.
|
Doors (non-temp rise)
|
552/3.83
|
12
|
46
|
Note: Individual lite sizes cannot exceed "Max. Exposed Area" shown above.
| Surface Finish |
Diamond |
Georgian |
| Max. Sheet Size |
58" X 100" |
58" X 100" |
This information is intended for general reference only. For current listing details, please call Technical Glass Products.
Framing Options


The Designer Series doors and frames incorporate precise European engineering, providing a sleek, modern alternative to traditional hollow metal frames.
Traditional Hollow Metal Steel Frames-Fire-Rated Doors & Frames

TGP glazing can be used in any approved fire-rated door and frame assemblies.
Storage & Handling
Inspect each piece of WireLite NT immediately before installation and eliminate any with observable edge damage or face imperfections.
WireLite NT must be handled with care during transportation, storage, inspection and installation. Store in a dry place.
Care & Warranty
TGP warrants only that the surface applied film will maintain peel adhesion without cracking, peeling, crazing, delaminating or discoloring during a period of 3 years from the date of purchase, providing the products have been properly shipped, stored, handled, installed and maintained. The remedy for surface applied film if proved to be defective under the terms of this warranty is limited to the replacement of the the film material only.
Feeling Social?
Check out our
social media sites.
Like us on Facebook, watch our YouTube videos, follow us on Twitter and stay tuned for a few other applications in the works. Interact, share ideas and learn about fire-rated glass and framing in a whole new way.